Ordinary pressure storage product hanging dry powder fire extinguishing device
Working principle of hanging dry powder fire extinguishing device for ordinary pressure storage products
This device is completely automatic from detecting a fire to extinguishing it, safe and efficient, without the need for personnel operation, easy to install, driven by nitrogen gas, with a storage pressure of 1.2MPa. Each device is equipped with a pressure indicator, and the operation status of the fire extinguishing device can be visually checked during daily maintenance. This device consists of a tank body, a nozzle, a glass ball electric initiator, and a pressure signal feedback device. A temperature sensing glass ball is installed on the nozzle, The operating temperature of the nozzle is generally 68 ℃, and the fire extinguishing agent is evenly sprayed under the drive of nitrogen gas; And there are multiple sets of linkage, undervoltage, and startup signal feedback functions.